Serija FX5 – analogni nadzorni moduli

Analogni vhodni moduli

Specifications FX3U-4AD FX5-4AD FX5-8AD
Applicable for Base units FX3G/FX3GC/FX3GE/ FX3U/FX3UC/ FX5U/FX5UC Base units FX5U/FX5UC
Analog channels Inputs 4 4 8
Outputs
Analog input range -10–10 V DC/-20–20 mA/4–20 mA -10–10 V DC/ -20–20 mA/ 4–20 mA User range setting -10–10 V DC/ -20–20 mA/ Temperature detector (K, J, T, B, R, S, Pt100, Ni100) 2
Resolution Voltage 0.32 mV (16 bit + sign) 0.3125 mV 0.3125 mV (16 bit + sign)
Current 1.25 µA (15 bit + sign) 0.625 µA 0.625 µA (16 bit + sign)
Fullscale overall accuracy ±0.3–1 % 1 ±0.1–0.3 % 1 ±0.3–±0.5 %
Power supply 5 V DC 110 mA (from base unit) 40 mA (from base unit)
24 V DC 9 mA 100 mA (from base unit) 100 mA (from external)40 mA (from base unit)
Related I/O points 8 8 8
Weight kg 0.2 0.2 0.3
Dimensions (WxHxD) mm 55x90x87 40x90x83 50x90x83
Order information Art. no. 169508 334430 312297

1. Dependent on the ambient temperature

Please refer to manuals for further details of specification of temperature detectors.

Notes: The FX2N-8AD can be configured to accept standard analog inputs as well as selected temperature inputs such as K, T or J type thermocouples. To connect these modules to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a ­FX3U-4AD to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

Analogni izhodni moduli

Specifications FX3U-4D A FX5U-4D A
Applicable for Base units FX3G/FX3GC/FX3GE/FX3U/FX3UC/FX5U/FX5UC Base units FX5U/FX5UC
Analog channels Inputs
Outputs 4
Analog output range -10–10 V DC/0–20 mA/4–20 mA -10–10 V DC/0–20 mA/4–20 mA User range setting
Resolution Voltage 0.32 mV (16 bit + sign) 125 µV
Current 0.63 µA (15 bit) 500 nA
Fullscale overall accuracy ±0.3–0.5 %* ±0.1–0.3 %*
Power supply 5 V DC 100 mA (from base unit)
24 V DC 160 mA 150 mA
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 55x90x87 40x90x83
Order information Art. no. 169509 325715

* Dependent on the ambient temperature

Notes : To connect these modules to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-4DA to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

Analogni I/O adapterji

Specifications FX5-4AD-ADP FX5-4DA-ADP
Analog channels Inputs 4
Outputs 4
Analog range -10–10 V DC, -20–20 mA -10–10 V DC, 0–20 mA
Resolution 312.5 µV/1.125 μA (14 bit ) 250 µV/1 μA (14 bit )
Overall accuracy ±0.1 %*/±0.3 % ±0.1 %*/±0.2 %
Power supply 5 V DC 10 mA (from base unit)
24 V DC 20 mA (from base unit) 160 mA (external power supply)
Related I/O points 0
Weight kg 0.1
Dimensions (WxHxD) mm 17.6×90(106)x89.1
Order information Art. no. 283559 283560

* Dependent on the ambient temperature and signal quality

 

Analogni vhodni temperaturni adapterji

Specifications FX5-4AD-PT-ADP FX5-4AD-TC-ADP
Applicable for Base units FX5U, FX5UC
Analog inputs 4 4
Compensated temperature range °C -200–+850 (Pt100)/ -60–+250 (Ni100) -40–+750(J)/ -200–+1200 (K)/ 0–1600(R, S)
Digital outputs -2000–+8500 (Pt100)/ -600–+2500 (Ni100) -400–+7500 (J)/ -2000–+12000 (K)/ 0–16000 (R, S)
Resolution °C 0.1 0.1 (K,J,T), 0.1–0.3 (B,R,S)
Fullscale overall accuracy ±0.4–2.4 °C (fullscale)* ±2.8–7.2 °C (fullscale)*
Power supply 5 V DC 10 mA 10 mA
24 V DC 20 mA 20 mA
Related I/O points 0 0
Weight kg 0.1 0.1
Dimensions (WxHxD) mm 17.6×90(106)x74(89.1)
Order information Art. no. 304298 304299

* Dependent on the ambient temperature

Notes : When connecting the FX3 analog adapters to a FX3G, FX3S or FX3U base unit, a communications adapter is required. A direct connection without adapter is possible if these modules are connected to a FX3GC, FX3GE or FX3UC base unit.

 

Temperaturni nadzorni moduli

Specifications FX5-4LC
Applicable for Base units FX5U, FX5UC
Analog inputs 4 (Thermocouple, Pt100 and Pt1000 sensors )
Compensated temperature range °C -200–+2300
Digital outputs 4 NPN transistor open collector output points
Resolution °C 0.1 °C, 1.0 °C, 0,5 µV or 5.0 µV; Varies depending on input range of used sensors
Fullscale overall accuracy
Power supply 5 V DC 140 mA (from base unit)
24 V DC 25 mA
Related I/O points 8
Dimensions (WxHxD) mm 60x90x83
Order information Art. no. 312298

Notes : To connect these modules to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX5U-4LC to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.



SODELUJMO!

Univerzalne rešitve na področju industrijske avtomatizacije, ki bi ustrezala vsem podjetjem, ni! Ker so naši kupci iz različnih panog, in ker se trudimo razumeti potrebe vašega podjetja, s pomočjo tehnične podpore znamo ponuditi ustrezno opremo.

Kontaktirajte nas