Serija FX3 – mrežna komunikacija

Specifications FX2N-32CCL
Module type Remote station
Link points per station I/O points 32
Register 8
Max. number of I/O points
Number of connectable modules
Power supply 5 V DC Max. 130 mA (from base unit)
24 V DC 50 mA
Related I/O points 8
Weight kg 0.3
Dimensions (WxHxD) mm 43x90x87
Order information Art. no. 102961

Notes: To connect this module to a FX3UC or FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required. More informations about CC-Link are available in various other publications from Mitsubishi Electric.

 

Specifications FX3U-CAN
Module type CANopen master
CANopen communication standard CiA 301 V4.2, CiA 302 V4.1, CiA 305 V2.2
CANopen Lift application profile mode CiA 417 V2.1
CANopen PLC device profile mode CiA 405 V2.0
Max. number of modules that can be connected to the network 30 without repeater; 127 with repeater
Station numbers 1–127
Supported communication speeds kbps 10, 20, 50, 125, 250, 500, 800, 1000
Status displays RUN, error, power, network status
Power supply 5 V DC 290 mA
24 V DC
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x88.7
Order information Art. no. 252845

Notes: To connect this module to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-CAN to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

 

Specifications FX3U-32DP
Module type Slave station
Transmission type Bus network
Transmission data Max. 144 bytes
Interface 9-pin D-SUB for Profibus DP
Max. number of slave stations per configuration 8
Communication speed 5 V DC Max. 12 Mbit/s
Communication distance 24 V DC Max. 1200 (depends on communication speed)
Communication cable Profibus cable with 9-pin D-SUB connector
Related I/O points 8
Power supply 24 V DC/145 mA (from base unit)
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x89
Order information Art. no. 194214

Note: To connect a FX3U-32DP to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.

 

Specifications FX3U-ENET/FX3U-ENET-P502 FX5-ENET
Applicable for Base units FX3G, FX3GC, FX3GE, FX3U, FX3UC Base units FX5U, FX5UC
Protocol TCP/IP, UDP
Communication mode Full-duplex/half-duplex
No. of simultaneous open connections 8
Fixed buffer communication 1023 word x 8
Communication with mail server SMTP, POP3
Interface IEEE802.3u (100BaseTX), IEEE802.3 (10BaseT)
CC-Link IE Field Network Basic Master
Connector RJ45 2xRJ45
Max. transfer rate 100 Mbits/s, 10 Mbit/s
Max. segment length m 100
Cable CAT5 STP or 3 STP
Power supply 5 V DC
24 V DC 240 mA (from base unit) 110 mA (from base unit)
Related I/O points 8
Weight kg 0.3 0.2
Dimensions (WxHxD) mm 55x90x87 40x90x83
Order information Art. no. 166086/225142 409823

Note: To connect this module to a FX3UC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required .

 

Specifications FX3U-64DP-M FX5-DP-M
Applicable for Base units FX3U, FX3UC Base units FX5U, FX5UC
Module type Master station
Transmission type Bus network
Transmission data 32 byte/slave (normal service mode) 244 byte/slave (extended service mode)
Interface Profibus DP (with 9 pole D-SUB connector)
Max. number of master per configuration Max. 1
Repeaters 3
Max. number of slaves 64
Communications speed Profibus standard
Communications distance m Max. 1200 (depends on communication speed)
Communication cable Profibus cable with 9-pin D-SUB connector
Power supply 5 V DC
24 V DC Max. 155 mA (from base unit) 150 mA (from base unit)
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x87 40x90x85.3
Order information Art. no. 166085 409822
Accessories Profibus connector up to 12 Mbaud: PROFICON-PLUS, art. no. 140008 or PROFICON-PLUS-PG, art. no. 140009

Notes : The FX3U-64DP-M can be used in combination with a FX3U or FX3UC base unit only. To connect this module to a FX3UC base unit, an adapter ­FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.

 

Specifications FX2N-64DNET
Module type Slave (group 2)
Node type G2 server
Station numbers 0–63 points
Supported communication speeds kbps 125/250/500
Communication data (open connection) Master/ slave No. of connections 1 connection (group 2)
Transfer time-out 2,000 ms (ACK time-out)
UCMM client/server No. of connections 63/63 (group 1, 3)
Data length Max. 64 bytes per connection
Communication data (I/O connection) Type Polling, cyclic, change of state
Data length Max. 64 bytes (fragmentation is possible)
Module ID code K 7090
Status displays Power, module status, network status
Related I/O points 8
Power supply 5 V DC 120 mA
24 V DC 50 mA
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x87
Order information Art. no. 131708

 

Specifications FX3U-485ADP-MB
Interface RS485; Modbus® RS485
Communication speed* kbps 0.3–19.2
Max. communication distance m 500
Power supply 5 V DC 20 mA (from base unit)
24 V DC
Related I/O points 0
Dimensions (WxHxD) mm 17.6×90(106)x74
Order information Art. no. 206191

* The communication method and communication speed vary depending upon the communication type.

Notes : This adapter module can be connected directly (without special adapter) to a base unit of the FX3GC, FX3GE or FX3UC series. To connect this adapter module to a FX3G, FX3S or FX3U base unit, an adapter is required.

 

Specifications FX2N-232IF
Interface RS232C with 9 pole D-SUB connector (photocoupler isolation)
Communication speed kbps 0.3–19.2
Communication distance m Max. 15
Communication cable Shielded cable
Communication mode Full duplex
Protocols Non protocol mode/start stop synchronisation
Send and receive buffer 512 byte each
Format 7 or 8 bits, parity none/even/odd, stop bits: 1 or 2
Power supply 5 V DC 40 mA (from base unit)
24 V DC 80 mA
Related I/O points 8
Weight kg 0.3
Dimensions (WxHxD) mm 55x90x87
Order information Art. no. 66640

Note: To connect this module to a FX3UC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required.

 

Specifications FX3U-CAN
Module type CANopen master
CANopen communication standard CiA 301 V4.2, CiA 302 V4.1, CiA 305 V2.2
CANopen Lift application profile mode CiA 417 V2.1
CANopen PLC device profile mode CiA 405 V2.0
Max. number of modules that can be connected to the network 30 without repeater; 127 with repeater
Station numbers 1–127
Supported communication speeds kbps 10, 20, 50, 125, 250, 500, 800, 1000
Status displays RUN, error, power, network status
Power supply 5 V DC 290 mA
24 V DC
Related I/O points 8
Weight kg 0.2
Dimensions (WxHxD) mm 43x90x88.7
Order information Art. no. 252845

Notes: To connect this module to a FX3UC/FX3GC base unit, an adapter FX2NC-CNV-IF or a power supply FX3UC-1PS-5V is required. For the connection of a FX3U-CAN to a FX5U/FX5UC base unit, a bus conversion module FX5-CNV-BUSC resp. FX5-CNV-BUS is required.

 

Specifications FX3U-ENET-ADP
Protocol TCP/IP
No. of simultaneous open connections 1
Interface IEEE802.3u (100BaseTX), IEEE802.3 (10BaseT)
Connector RJ45 (to Ethernet), 3 screw terminals (to ground)
Max. transfer rate 10 Mbit/s, 100 Mbit/s
Cable CAT5 STP or 3 STP
Power supply 5 V DC 30 mA (from base unit)
24 V DC
Related I/O points 0
Weight kg 0.1
Dimensions (WxHxD) mm 23×90(106)x81.5
Order information Art. no. 248844

Notes : This module can be connected directly (without adapter) to a base unit of the FX3GC or FX3UC series. To connect this module to a FX3G, FX3S or FX3U base unit, an adapter is required.

 

Specifications FX2N-32DP-IF-D
Power supply 24 V DC (+20 %/-30 %)
Power consumption 14 W
Internal current consumption 5 V DC/max. 220 mA (from base unit)
Interface (connectors) 9-pin D-SUB for Profibus DP, 8-pin Mini-DIN for PC or programming unit FX-10P/FX-20P/FX-30P
Communicationspeed 1200 m kbps 9.6/19.2/45.45/93.75
1000 m kbps 187.5
400 m kbps 500
200 m kbps 1500
100 m kbps 3000/6000/12000
Communication distance m Max. 1200 (depends on communication speed)
Communication cable Profibus cable with 9-pin D-SUB connector
Max. number of controllable I/O points 256
Weight kg 0.4
Dimensions (WxHxD) mm 75x98x87
Order information Art. no. 142763

 

 



SODELUJMO!

Univerzalne rešitve na področju industrijske avtomatizacije, ki bi ustrezala vsem podjetjem, ni! Ker so naši kupci iz različnih panog, in ker se trudimo razumeti potrebe vašega podjetja, s pomočjo tehnične podpore znamo ponuditi ustrezno opremo.

Kontaktirajte nas